electrical question extending wires on a cooktop... and safety?
I have a cooktop.. wires coming out of it were cut at base of unit and i need to extend them. I already did and am now concerned my work is not safe... the wires appear to be stranded 10 guage. I extended them with aluminum connectors that have set screws and then taped the hell ot of them. The wire I connected them to is ten guage.. the unit now says it takes a 40 amp cir and to use 8 guage wire... is this safe? shoudl I just use a 30 amp breaker instead?
You do not determine whether or not the connector is appropriate by determining what it is made from etc. The manufacturer of the connector provides information on whether the connector is for copper only (Cu), copper and aluminum (Cu/Al) or just aluminum wire (Al). The manufacturer also determines the number of solid and/or stranded wires and the maximum and minimum wire size that can be safely connected with the connector. The rating of the connector is reviewed by an independent agency such as Underwriters Laboratories (UL) or the Canadian Standards Association (CSA).
The current rating of wire is not determined only by the wire size and whether the wire is stranded or solid. The temperature rating of the insulation, the maximum temperature of the air and the terminals to which the wire is fastened, the number of wires that are bundled together and other factors determine the current rating. Electrical codes list the current ratings for the types of wiring normally used to wire buildings. Manufacturers are responsible for wire inside their products subject to review by UL, CSA etc.
I believe that it would be unusual for a cooktop to be furnished with lengths of wire for connection to the power supply for installation. Look to see if there is a cover that can be removed for access to screw terminals where the installation wiring should be attached. If terminals are furnished, remove the wires that have been cut off and replace them with wires of appropriate size, length and type. If you must splice the wires, the applicable electrical code probably requires the splice to be enclosed in an appropriate electrical box. If you are going to do this work yourself, at a minimum, you should go to the library and review the appropriate electrical codes. It would be better to hire a qualified electrician.
![]() |
![]() 6 Sterling Silver 3 Strand Bead Connectors 85 x 8mm $11.50 Time Remaining: 3d 12h 56m Buy It Now for only: $11.50 |